Theme

LED Emergency Luminaire

LED Emergency Luminaire Head

Overview

LED Emergency Luminaire comprising a 50mm diameter lamp unit containing charge indicator and white power LED with articulated box enclosing driver, charger and battery. This luminaire can easily be fed through ceiling cut outs of 42mm diameter. Available in both maintained and non-maintained versions.

LED Emergency Luminaire

Features

  • 3W non-maintained or maintained self contained emergency fixture with white LED
  • Latest LED technology
  • Self testing features to IEC 62034, plus audiable alarm
  • 16 hour charge, 3 hour duration in emergency mode
  • Can be installed through ceiling cut outs of 42mm in diameter
  • Smart charge intermittent charging reduces battery temperature
  • Incorporates high quality 3.6V 2.7Ah NiMH battery pack
  • Built in reflector achieves efficient output
  • Ambient temperature of 0° to 30°
  • Integral bi-colour indicator LED

Materials and Finishes

LED HeadMoulded Plastic with Die-cast Heatsink
Articulated BoxMoulded Plastic

Technical Details

GearNon-maintained Emergency with Nickel Metal Hydride Battery Pack
Lamp Type3W LED running at 2W giving 64 lumen.
  • LEDLED

Operation

The Emergency LED luminaire provides full auto testing functions in accordance with IEC 62034. This includes a commission period, 30 second functional test monthly and full duration test annually.

Audiable alarm will sound if a fault is found during a test and will continue to give three beeps every 35 minutes until the fault is rectified.

Indicator LEDDescription
LED Green with 10 second BlinkNormal standby mode, mains connected, charging, battery and power LED satisfactory.
LED Green Slow FlashCommissioning mode or duration test in progress.
LED Green Fast FlashFunctional test in progress
LED OffMains not connected
LED Red Slow FlashBattery or charging system fault
LED Red Fast FlashDefective power LED

Dimensions

Overall length of 415mm (Module and battery box can be installed in cut outs of 42mm in diameter)

Ordering

Order CodeDescriptionWeight
LEDELMMaintained* version320g
LEDELNMNon-maintained** version320g

* Maintained mode - where power LED will operated during mains healthy conditions and during the event of a power failure

** Non-maintained mode - where power LED is only illuminated when the mains power fails

Suitable for mounting on flammable surfaces European Conformity Mark Isolation Class 2