Gemlite
Overview
The improved Gemlite is a specialised dual function, recessed modular luminaire dedicated to the
lighting of intensive care units. The Gemlite has been developed with the assistance of ICU specialists.
Features
- Offers two distinct light levels from one fitting. Thus meeting CIBSE recommendations for bedded areas and examinations
- Rapid switching to higher light intensity via G100/3 dimming controller
- Designed to comply with clean room standards with clear acrylic cover to facilitate cleaning
- Ceiling mounted and therefore independent of mobile ICU equipment, there is an absence of interference with sensitive monitoring or diagnostic systems
- Supplied with side arm fixing brackets as standard, to facilitate fixing in plasterboard or exposed 'T' ceilings. Alternatively, drop rods may be fitted
- Surface mounted versions available to order (please refer to our technical department for special installation requirements)
- IP54 rated
- 4000K lamps recommended for hospital use
Materials and Finishes
| Body | 1mm Zintec Steel |
| Controller | Asymmetric Square Cell Panel and a Prismatic Panel |
| Finish | White |
Technical Details
| Gear | High Frequency and High Frequency Dimmable (Requires use of G100/3 Dimming Controller) |
| Lamp Type |
PLL
|
Dimensions
| | L | W | R |
| Gemlite | 677 | 598 | 145 |
| C (Cut Out) | 575 | 575 | - |
Design
|
|
|
CIBSE recommended illuminance levels for bedded area lighting is 400 lux
|
|
|
|
CIBSE recommended illuminance levels for examination lighting is 1000 lux
|
Please note that the proposed location for optimum designed performance of this luminaire is determined by the following parameters
- Ceiling height
- Bed height/position
- Specific medical use
- Ceiling type/construction
It is vital that the bed position and the luminaire position are accurately located in relation to each other at the design and installation stages
Ordering
All versions supplied excluding lamps.
| Order Code | Description | Lamp Type & Rating | Gear | Weight (kg) |
| GE455D/2 | Gemlite | 4x55W PLL | HF+HFD | 15.2 |
Emergency
| E | Maintained 3hr Emergency Integral |
Accessories
| G100/3 | Dimming Controller (required as standard) |