Theme

G100

G100/2

Overview

The G100/2 has been specifically designed for use with the Apollo Gemlite (see healthcare section), in order to meet the three lighting level requirements necessary for intensive care overbed illumination. These being 'general' lighting appropriate for day to day observation and care without discomfort to patients; 'night' lighting appropriate for observation requirements with minimum disturbance to sleeping patients; and high intensity 'examination' lighting levels for close observation and treatment.

Suitable for flush or surface mounting installation as required.

Operation

  • To achieve general lighting as described above, turn on switch 'A' (see diagram).
  • To achieve night lighting set to required dimmed level via the rotary controller.
  • To achieve high intensity examination lighting turn on switch 'B' (see diagram). Switch 'B' overrides switch 'A' and the rotary controller to give full light output, regardless of the previous setting of the luminaire.

In order to avoid accidental loss of light during critical situations, once activated, the high intensity examination level will be maintained until both switches 'A' and 'B' are switched off. This will reset the luminaire ready for normal operation.

Technical Details

Rotary Switch Contacts1A resistive rating. Not to be used to switch dimmable ballasts due to inrush currents
Rotary Switch Terminals4 screw terminals (two for the 1-10V DC and two for the 240V mains switch)
White Mains Switch Contacts20A nominal rating, single gang, single pole, two way
White Mains Switch Terminals4.0mm² conductors
Red Mains Switch Contacts20A nominal rating, single gang, single pole, two way
Red Mains Switch Terminals4.0mm² conductors
MountingSuitable for installation on 72x135x41mm BS box (not supplied)

Dimensions

g100/2 Dimensional Diagram
 WH
G100/213572

Ordering

Order CodeDescription
g100/2Dimming controller

Some luminaires have more than one ballast, if there is any doubt, please consult our techincal department. If more than 12 luminaires are to be operated then an additional relay or contactor should be used.

The 1-10V DC control cable should be mains insulated and run separately, or screened from the mains cable.

Please ensure new lamps are conditioned at full output for 100 hours prior to being dimmed.