Theme

Control Gear Table

The following table shows some typical values for single pole MCB's, the figures are based on Type C breakers with a rating of 10 Amp and the circuit wired with 1.5mm cable.

For multi-pole MCB's it is advisable to reduce the number of ballasts by 20 percent.

Linear Fluorescent

Lamp Type Lamp Qty/Wattage Switchstart High Frequency HF Quantity per Breaker
System Watts System Watts
T5 16mm 1x14W-1746
2x14W-3146
3x14W-5230
4x14W-6630
1x21W-2546
2x21W-4746
3x21W-72-
4x21W-94-
1x28W-3244
2x28W-6218
3x28W-94-
4x28W-124-
1x35W-3946
2x35W-7620
1x24W-2846
2x24W-5230
1x39W-4230
2x39W-8418
1x54W-6030
2x54W-11714
1x49W-5430
2x49W-11118
1x80W-8618
T8 26mm 1x18W282046
2x18W453844
3x18W7358-
4x18W9074-
1x36W463646
2x36W927220
3x36W138108-
4x36W184114-
1x58W715532
2x58W14211014

Compact Fluorescent

Lamp Type Lamp Qty/Wattage Switchstart High Frequency HF Quantity per Breaker
System Watts System Watts
2D 1x16W22--
1x21W---
1x28W363132
1x38W483920
1x55W-5814
PLC 1x10W1612.546
1x13W171446
1x18W242048
2x18W483848
1x26W342834
2x26W685422
PLL 1x18W282030
2x18W453730
1x24W332630
2x24W665130
1x36W463680
2x36W927220
1x40W494530
2x40W988914
1x55W-5820
2x55W-11610
PLT 1x13W-1346
1x18W-1848
1x32W-3632
2x32W-7222
3x32W-108-
1x42W-4734
2x42W-9614
3x42W-143-

Circular T5

Lamp Type Lamp Qty/Wattage High Frequency HF Quantity per Breaker
System Watts
T5C 1x22W26-
1x40W46-
1x55W61-
1x60W64-

Others

Lamp Type Lamp Wattage Voltage PFC Capacitor Circuit Watts Quantity per Breaker
SON 50W230106116
70W230128112
100W2301211410
150W230201667
250W230362765
400W230454233
1000W23010010371
Metal Halide 35W23064322
70W230128212
150W230201707
250W230322725
400W230354343
1000W2308510721
2000W3806021001