Manufacturing in the UK since 1989

Genius CON-X

Genius CON-X

Overview

The Genius CON-X system provides a quick and easy solution to your room requirements that will reduce energy costs whilst increasing user convenience. Built around a lighting control module loaded with pre-configured room scenes, the system allows simple scene adjustment to suit a host of different room scenarios.

Incorporating graduated dimming, the system offers maximum energy savings whilst being very easy to install. Using the pre-fixed connecting leads on each luminaire enables quick connection to the lighting control module and significantly reduces installation time.

The system comes complete with microwave detector, lighting control module and connecting leads, with an optional scene plate for simple scene selection.

Features

Versatile
A wide range of recessed, surface mounted and suspended luminaires are available on request for the Genius CON-X system.
Compatible
Works with any DALI dimming equipped luminaires
Easy Installation
All the luminaires are supplied complete with plugs on 8m leads to enable easy, plug and play installation. Scene plates and detectors are supplied with 10m leads.
Graduated Dimming
Ideal for maximising the use of daylight within a space. The luminaires will progressively dim from the natural light source, in response to changes of the natural light levels. This prevents over lighting the space and minimises energy consumption.
Scene Setting
Recall a pre-programmed scene to create specific lighting scenes to suit different uses within the classroom environment, a white board scene.
Simple Commissioning
Commissioning is easy with the Genius CON-X system, simply select the configuration you desire on the handset and send to the LCM and you have a complete commissioned system. Perfect for quick re-commissioning when there is a change in the room usage.
Emergency Lighting Test
A local emergency test can be carried out by adding an emergency test switch to the dedicated SELV input. This can be linked across multiple lighting control modules to enable a number of rooms to be tested from a single key switch.
Corridor Hold
By connecting the corridor hold output between multiple lighting control modules, create a simple notional corridor route which will provide safe local egress lighting.
SELV Switching
The lighting control modules can have up to 5 centre biased retractive switches connected, including an emergency lighting test switch. This allows non-mains rated cabling to be used for the manual switches without the need for mechanical protection.

Product Dimensions

Lighting Control Module Dimensional Diagram

L H3 W H1 H2 150 200 127
LWH1H2H3
Lighting Control Module3951474352170

Scene Plate Dimensional Diagram

W D R H 60.3
HWDR
Scene Plate8686513

Specifications

Lighting Control Module

Casing
Flame retardant ABS and PC/ABS
Supply Voltage
220–240V AC
Frequency
50Hz
Relay Rating
Switched live : 10A
Switched permanent live : 6A
Terminal Capacity
Mains : 4mm² in wiring compartment
Switched inputs : 1.5mm² in wiring
Load per LCM
10A
Max Load per Channel
6A subject to maximum LCM limit of 10A
3A low energy lighting
Dimming
Maximum of 50 per LCM, subject to maximum 10A LCM limit:
100m using 0.5mm² wire
150m using 1.0mm² wire
300m using 1.5mm² wire
Temperature Range
−10°C to 35°C
Humidity
5–95% non-condensing
Insulation
Class II
Compliance
EMC-2004/108/EC
LVD-2006/95/EC
Weight
1.0kg

Scene Plate

Casing
Flame retardant ABS and PC/ABS
Supply Voltage
12V DC
Terminal Capacity
1.5mm²
Humidity
5–95% non-condensing
Temperature Range
−10°C to 35°C
Compliance
EMC-89/336/EEC
LVD-72/23/EEC

Associated Items

Example Configuration

Genius CON-X 3×4 Preset 10

Office/Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.
SW1 SW2 SW3 Whiteboard Switch ASENS-C6MW-PRO Windows Whiteboard CH7 CH6 CH5 CH4 CH3 CH2 CH1 20% 60% 100% Graduated Dimming
  • SW1, SW2 & SW3. Each switch operates luminaires within the same colour group.
  • Whiteboard Switch. Switches and dims the whiteboard luminaires within the associated group.
  • All luminaires are dimmable, with daylight linked graduated dimming from window row.
  • Upon exiting the space any luminaires left on will switch off after an adjustable time period.

Example Configuration

Genius CON-X 3×4 Preset 40

Office/Classroom with 3 rows of luminaires switched individually. Whiteboard on channel 2. Scene plate by teacher's desk. Detector for lux (scene 1 only) and absence.
SW1 SW2 SW3 Whiteboard Switch ASENS-C6MW-PRO Windows Whiteboard CH7 CH6 CH5 CH4 CH3 CH2 CH1 20% 60% 100% Scene Plate Graduated Dimming
  • SW1, SW2 & SW3. Each switch operates luminaires within the same colour group.
  • Whiteboard Switch. Switches and dims the whiteboard luminaire independently.
  • All luminaires are dimmable, with daylight linked graduated dimming from window row on scene 1 only.
  • Upon exiting the space any luminaires left on will switch off after an adjustable time period.
  • Scene Setting 1. All luminaires at 100% (with graduated daylight link).
  • Scene Setting 2. All luminaires at 75%. Whiteboard luminaire switched off.
  • Scene Setting 3. All luminaires at 50%.
  • Scene Setting 4. All luminaires at 25%.

Genius Solution Builder

Use the options below to define your Genius CON-X solution.

Note

An ASENS-CHSLCD Advanced LCD Programming Handset MUST be ordered to enable selection of pre-programmed scenes.

Genius CON-X Kit

Controls Kit

Accessories

GENEDS1
1 Switch Plate (1 CB Retractive Switch)
GENEDS2
2 Switch Plate (1 CB Retractive Switch + 1 Em. Key Switch)
GENEDS3
3 Switch Plate (3 CB Retractive Switches)
GENEDS4
4 Switch Plate (3 CB Retractive Switches + 1 Em. Key Switch)
GENEDS7
7 Button Scene Selector Plate in White
GENEDSE
Emergency Key Switch
GENEDSW
Whiteboard Switch
1ASENS-CHSLCD
Advanced LCD Programming Handset
Caveats
11 × ASENS-CHSLCD MUST be ordered to enable selection of pre-programmed scenes.

Apollo Lighting Ltd

Unit D9 Cross Green Approach
Leeds
LS9 0SG

Tel: 0113 240 5511

Fax: 0113 240 5151

Web: www.apollolighting.co.uk